Quickly verify wire capacity and maximum fill limits for EMT, Schedule 40/80 PVC, and RMC conduits per NEC Table 1 & Table 4.
Actual Fill %
34.2%
Max Allowed: 40%
Conductor Area
0.0728 sq in
4 total conductors
Conduit Usable Area
0.213 sq in
40% of 3/4" EMT
VoiceBid turns jobsite voice notes into an itemized 3-tier bid with NEC code notes and homeowner e-sign.
| Conduit Size & Type | Max 14 AWG | Max 12 AWG | Max 10 AWG | Max 8 AWG | Max 6 AWG |
|---|---|---|---|---|---|
| 1/2" EMT (0.122 sq in @ 40%) | 12 | 9 | 5 | 3 | 2 |
| 3/4" EMT (0.213 sq in @ 40%) | 22 | 16 | 10 | 5 | 4 |
| 1" EMT (0.346 sq in @ 40%) | 35 | 26 | 16 | 9 | 6 |
| 1-1/4" EMT (0.598 sq in @ 40%) | 61 | 45 | 28 | 16 | 11 |
Per NEC Chapter 9, Table 1, the maximum allowable conduit fill is 53% for 1 conductor, 31% for 2 conductors, and 40% for 3 or more conductors. These limits apply across all raceway types (EMT, PVC, RMC, and FMC) to prevent conductor jamming during wire pulls and prevent excessive heat buildup.
A 3/4" EMT conduit holds up to 16 conductors of 12 AWG THHN wire at the 40% NEC fill limit. For a 1/2" EMT conduit, the limit is 9 conductors of 12 AWG THHN.
A 3/4" EMT conduit holds up to 10 conductors of 10 AWG THHN wire at the 40% fill limit. If upsizing to a 1" EMT conduit, the maximum capacity increases to 16 conductors.
Yes, equipment grounding conductors (EGC) must always be included in the conduit fill calculation. Per NEC Chapter 9, Note 1, all conductors installed in a conduit, whether insulated, bare, grounded, or ungrounded, occupy physical cross-sectional space and count toward the total fill percentage.