NEC 2023 Chapter 9

Conduit Fill Calculator

Quickly verify wire capacity and maximum fill limits for EMT, Schedule 40/80 PVC, and RMC conduits per NEC Table 1 & Table 4.

Quick Presets:
1. Conduit Type & Size
2. Conductors (THHN / THWN-2)

Calculation Results

PASS (NEC Compliant)

Actual Fill %

34.2%

Max Allowed: 40%

Conductor Area

0.0728 sq in

4 total conductors

Conduit Usable Area

0.213 sq in

40% of 3/4" EMT

Max Wire Capacity for 3/4" EMT (40% Fill Limit)

Bidding this conduit run or panel feed?

VoiceBid turns jobsite voice notes into an itemized 3-tier bid with NEC code notes and homeowner e-sign.

Draft Proposal → Sample preview

NEC Conduit Fill Capacity Quick Reference & FAQs

Conduit Size & Type Max 14 AWG Max 12 AWG Max 10 AWG Max 8 AWG Max 6 AWG
1/2" EMT (0.122 sq in @ 40%) 12 9 5 3 2
3/4" EMT (0.213 sq in @ 40%) 22 16 10 5 4
1" EMT (0.346 sq in @ 40%) 35 26 16 9 6
1-1/4" EMT (0.598 sq in @ 40%) 61 45 28 16 11
*Values based on THHN/THWN conductors per NEC Chapter 9 Table 1 & Table 4.

What is the maximum conduit fill percentage according to the NEC?

Per NEC Chapter 9, Table 1, the maximum allowable conduit fill is 53% for 1 conductor, 31% for 2 conductors, and 40% for 3 or more conductors. These limits apply across all raceway types (EMT, PVC, RMC, and FMC) to prevent conductor jamming during wire pulls and prevent excessive heat buildup.

How many 12 AWG THHN wires fit in a 3/4 inch EMT conduit?

A 3/4" EMT conduit holds up to 16 conductors of 12 AWG THHN wire at the 40% NEC fill limit. For a 1/2" EMT conduit, the limit is 9 conductors of 12 AWG THHN.

How many 10 AWG THHN wires fit in a 3/4 inch EMT conduit?

A 3/4" EMT conduit holds up to 10 conductors of 10 AWG THHN wire at the 40% fill limit. If upsizing to a 1" EMT conduit, the maximum capacity increases to 16 conductors.

Does the equipment grounding wire count toward conduit fill?

Yes, equipment grounding conductors (EGC) must always be included in the conduit fill calculation. Per NEC Chapter 9, Note 1, all conductors installed in a conduit, whether insulated, bare, grounded, or ungrounded, occupy physical cross-sectional space and count toward the total fill percentage.

Service Load Calculator (NEC 220) Wire Ampacity Chart (NEC 310.16) EV Charger Sizer Voltage Drop Calculator Joist Alternative ServiceTitan Alternative Jobber Alternative Housecall Pro Alternative