VoiceBid
Calculate the voltage drop of an electrical circuit based on wire size, distance, and load.
Voltage Drop
0.00 V
Voltage Drop %
0.00%
NEC Recommended < 3%
End of Circuit Voltage
0.00 V
Max 3% Distance
0 ft
Before exceeding 3%
Warning: Voltage drop exceeds the recommended 3% for branch circuits.
VoiceBid turns jobsite voice notes into an itemized 3-tier bid with NEC code notes and homeowner e-sign.
| Circuit Load & Voltage | Standard Wire | Max Run (< 3% Drop) | Upsized Wire Size | Upsized Max Run |
|---|---|---|---|---|
| 15A Circuit @ 120V (12A continuous) | 14 AWG Cu | 50 ft | 12 AWG Cu | 75 ft |
| 20A Circuit @ 120V (16A continuous) | 12 AWG Cu | 60 ft | 10 AWG Cu | 90 ft |
| 30A Dryer/HVAC @ 240V (24A continuous) | 10 AWG Cu | 120 ft | 8 AWG Cu | 190 ft |
| 50A Range/Subpanel @ 240V (40A load) | 6 AWG Cu | 180 ft | 4 AWG Cu | 290 ft |
| 60A EV Charger @ 240V (48A continuous) | 6 AWG THHN Cu | 150 ft | 4 AWG Cu | 240 ft |
Per NEC Informational Notes 210.19(A) and 215.2(A)(1), the recommended maximum voltage drop is 3% for any individual branch circuit or feeder, and a maximum of 5% total across the combined feeder and branch circuit to the farthest outlet. Keeping voltage drop under 3% ensures optimal equipment efficiency and prevents motors and electronics from overheating.
For single-phase AC circuits, the formula is VD = (2 × K × I × L) / CM. For 3-phase circuits, the formula is VD = (1.732 × K × I × L) / CM. K is conductor resistivity (approx. 12.9 ohms-cmil/ft for copper, 21.2 for aluminum), I is load current in amperes, L is one-way circuit length in feet, and CM is conductor cross-sectional area in circular mils.
For standard 120V branch circuits, wire should typically be upsized by one AWG gauge for runs exceeding 50 to 75 feet under full load. For example, a 20A circuit carrying 16A continuous on 12 AWG copper will exceed the 3% voltage drop threshold beyond 60 feet and requires 10 AWG copper.