VoiceBid
Interactive conductor sizing and derating field guide per 2020/2023/2026 National Electrical Code. Compute adjusted ampacity for ambient attic heat and conduit wire bundling instantly.
| Wire Size AWG / kcmil |
Copper (Cu) Conductors | Aluminum / Copper-Clad (Al) | ||||
|---|---|---|---|---|---|---|
| 60°C TW, NM-B |
75°C THW, Terminals |
90°C THHN, XHHW |
60°C TW, UF |
75°C THW, Terminals |
90°C THHN, XHHW |
|
VoiceBid turns jobsite voice notes into an itemized 3-tier bid with NEC code notes and homeowner e-sign.
Per NEC 334.80, the final allowable ampacity of Type NM-B (Romex) cable must not exceed the 60°C rating in Table 310.16. However, you are permitted to use the 90°C rating as the starting baseline when applying derating factors for hot attic ambient temperatures and conduit wire bundling, provided the final calculated ampacity does not exceed the 60°C column value (e.g., 15A for 14 AWG, 20A for 12 AWG, 30A for 10 AWG).
NEC 240.4(D) small conductor rules mandate that overcurrent protection for 14 AWG copper cannot exceed 15A, 12 AWG copper cannot exceed 20A, and 10 AWG copper cannot exceed 30A for general branch circuits. The extra ampacity shown in the 90°C column (30A for 12 AWG) serves as a buffer during derating calculations for ambient heat and raceway bundling so that the conductor does not drop below 20A capacity.
For equipment rated 100A or less (or marked for 14 AWG to 1 AWG), conductor ampacity must be selected from the 60°C column unless terminals are listed and marked for 75°C. Most modern circuit breakers and distribution panels have 75°C terminals. Even when pulling 90°C rated wire (such as THHN or XHHW), the conductor's final termination rating cannot exceed the lowest temperature rating of any connected termination (typically 75°C).
NEC Table 310.16 and Table 310.15(B)(16) are the exact same ampacity table with identical values. In the 2011, 2014, and 2017 NEC editions, the table was renumbered to Table 310.15(B)(16). Starting in the 2020 NEC and retained in the 2023 and 2026 editions, the NFPA restored the table's historic designation back to Table 310.16.
Per NEC 310.15(C)(1), when more than 3 current-carrying conductors are installed in a raceway or cable, ampacity must be derated by 80% for 4–6 wires, 70% for 7–9 wires, and 50% for 10–20 wires. Equipment grounding conductors and neutral wires carrying only unbalanced single-phase return currents are not counted as current-carrying conductors.