Size circuit breakers, wire gauges (THHN vs Romex NM-B), conduit trade sizes, and voltage drops for Level 2 EVSE installations according to National Electrical Code requirements.
Dedicated 2-Pole Breaker
60 A
125% of continuous load (NEC 625.42)
Minimum Conductor Size
#6 AWG Cu
THHN Copper (75°C)
Max Continuous Draw
48 A @ 240V
11.52 kW Charging Rate
Voltage Drop (% / Volts)
1.2% (2.88V)
Terminal: 237.12V (Good <3%)
Min. Conduit Trade Size
3/4" EMT
Per NEC Ch. 9 (40% fill)
Est. Charge Speed
~44 mi / hr
Adds ~250-300 mi overnight
VoiceBid turns jobsite notes into an itemized 3-tier proposal (Plug-In, Hardwired, Subpanel) with digital signature.
| Charger Output | Breaker (125%) | THHN Copper (Conduit) | NM-B Romex (60°C) | Charge Speed |
|---|---|---|---|---|
| 16A Level 2 | 20A 2-Pole | 12 AWG Cu | 12 AWG Cu | ~14 mi / hr (3.8 kW) |
| 24A Level 2 | 30A 2-Pole | 10 AWG Cu | 10 AWG Cu | ~22 mi / hr (5.8 kW) |
| 32A (NEMA 14-50) | 40A 2-Pole | 8 AWG Cu | 8 AWG Cu | ~30 mi / hr (7.7 kW) |
| 40A (NEMA 14-50 max) | 50A 2-Pole | 6 AWG Cu | 6 AWG Cu | ~37 mi / hr (9.6 kW) |
| 48A (Hardwired Wall Box) | 60A 2-Pole | 6 AWG Cu | 4 AWG Cu (6 NM-B prohibited) | ~44 mi / hr (11.5 kW) |
A 48-amp Level 2 EV charger requires a 60-amp 2-pole circuit breaker and 6 AWG copper THHN conductors in conduit (or 4 AWG NM-B Romex cable). Per NEC 625.42, EV charging is defined as a continuous load, requiring the branch circuit breaker and conductors to be sized at 125% of the charger's maximum current draw (48A × 1.25 = 60A).
Per NEC 334.80, Type NM-B (Romex) cable must be sized strictly from the 60°C column of Table 310.16, where 6 AWG copper is only rated for 55 amps. Because EV charging is a continuous load, installing 6 AWG Romex on a 60A breaker creates an overheating hazard and violates code. To install a 60A breaker, you must either upsize to 4 AWG Romex (rated 70A at 60°C) or pull 6 AWG THHN copper wire in conduit (rated 65A at 75°C terminals).
A standard NEMA 14-50 EV receptacle requires a 50-amp 240V double-pole circuit breaker and 6 AWG copper wire. Under the NEC 125% continuous duty rule, plug-in EV chargers connected to a 50A outlet must be capped at 40 amps maximum continuous load. Furthermore, NEC 210.8(A) requires GFCI breaker protection on all 240V garage and outdoor receptacles.