NEC 625.42 Continuous Duty Standard

EV Charger Wire & Breaker Calculator

Size circuit breakers, wire gauges (THHN vs Romex NM-B), conduit trade sizes, and voltage drops for Level 2 EVSE installations according to National Electrical Code requirements.

Quick Presets:
Max continuous current output from the EVSE unit.
NEC 210.8(A) requires GFCI breakers for receptacles.
NM-B Romex is restricted to 60°C ampacity tables.
Length of conduit / cable from main/sub panel to charger.

Recommended Circuit Specifications

Dedicated 2-Pole Breaker

60 A

125% of continuous load (NEC 625.42)

Minimum Conductor Size

#6 AWG Cu

THHN Copper (75°C)

Max Continuous Draw

48 A @ 240V

11.52 kW Charging Rate

Voltage Drop (% / Volts)

1.2% (2.88V)

Terminal: 237.12V (Good <3%)

Min. Conduit Trade Size

3/4" EMT

Per NEC Ch. 9 (40% fill)

Est. Charge Speed

~44 mi / hr

Adds ~250-300 mi overnight

Quoting this EV Charger run for a customer?

VoiceBid turns jobsite notes into an itemized 3-tier proposal (Plug-In, Hardwired, Subpanel) with digital signature.

Draft Proposal → Sample preview

EV Charger Wire & Breaker Sizing Quick Reference (NEC 625)

Charger Output Breaker (125%) THHN Copper (Conduit) NM-B Romex (60°C) Charge Speed
16A Level 2 20A 2-Pole 12 AWG Cu 12 AWG Cu ~14 mi / hr (3.8 kW)
24A Level 2 30A 2-Pole 10 AWG Cu 10 AWG Cu ~22 mi / hr (5.8 kW)
32A (NEMA 14-50) 40A 2-Pole 8 AWG Cu 8 AWG Cu ~30 mi / hr (7.7 kW)
40A (NEMA 14-50 max) 50A 2-Pole 6 AWG Cu 6 AWG Cu ~37 mi / hr (9.6 kW)
48A (Hardwired Wall Box) 60A 2-Pole 6 AWG Cu 4 AWG Cu (6 NM-B prohibited) ~44 mi / hr (11.5 kW)
*Based on NEC 625.42 continuous duty sizing (125% factor) and NEC 310.16 ampacity.

What size wire and breaker is needed for a 48 amp Level 2 EV charger?

A 48-amp Level 2 EV charger requires a 60-amp 2-pole circuit breaker and 6 AWG copper THHN conductors in conduit (or 4 AWG NM-B Romex cable). Per NEC 625.42, EV charging is defined as a continuous load, requiring the branch circuit breaker and conductors to be sized at 125% of the charger's maximum current draw (48A × 1.25 = 60A).

Why can't I use 6 AWG Romex (NM-B) on a 60 amp breaker for an EV charger?

Per NEC 334.80, Type NM-B (Romex) cable must be sized strictly from the 60°C column of Table 310.16, where 6 AWG copper is only rated for 55 amps. Because EV charging is a continuous load, installing 6 AWG Romex on a 60A breaker creates an overheating hazard and violates code. To install a 60A breaker, you must either upsize to 4 AWG Romex (rated 70A at 60°C) or pull 6 AWG THHN copper wire in conduit (rated 65A at 75°C terminals).

What breaker and wire size is required for a NEMA 14-50 EV receptacle?

A standard NEMA 14-50 EV receptacle requires a 50-amp 240V double-pole circuit breaker and 6 AWG copper wire. Under the NEC 125% continuous duty rule, plug-in EV chargers connected to a 50A outlet must be capped at 40 amps maximum continuous load. Furthermore, NEC 210.8(A) requires GFCI breaker protection on all 240V garage and outdoor receptacles.

Service Load Calculator (NEC 220) Wire Ampacity Chart (NEC 310.16) Conduit Fill Calculator Voltage Drop Calculator Joist Alternative ServiceTitan Alternative Jobber Alternative Housecall Pro Alternative